ADW2XX series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits,Up to four three-phase loop current inputs can be connected simultaneously.It Can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.
Multi-circuits Monitoring Monitor up to 4 circuits 3-phase or 12 circuits 1-phase Paired CTs with specs of 5A/1.25mA; 100A/20mA; 400A/100mA or 600A/100mA External CTs Connectwith ADW210 Main Body thrrough RJ12 Interface |
|
Expanded Communication Module --- AWT100 4G (Global general module) WiFi LoRaWAN LoRa NB-IoT |
|
Cable Temperature&Residual Current Measurement Module --- MTL Temperature Measurement:-20ºC~+100ºC Residual Current Measurement:10~3000 mA Accuracy:Temperature:± 2ºC; Residual Current:1% (Class 1) |
|
DO/DI Switch Extra Function Module --- MK 12 channel DI (Digital Input) 4 channel DO (Digital Output) |
Function
|
Description
|
|||
Energy
Measurement
|
kWh (positive and negative)
|
|||
kvarh (positive and negative)
|
||||
A,B,C three-phase positive kWh
|
||||
Electric Parameter
|
U, I, P, Q, S, PF, Hz
|
|||
Harmonic
|
2-31st voltage and current harmonic
|
|||
Communication
|
RS485 (MODBUS-RTU); baud rate 1200~38400
|
|||
Key Programming
|
4 keypads to set communication and parameters
|
|||
Display
|
LCD display, 8 digits
|
|||
LED Alarm
|
Over-voltage, over-current, interruption phase
|
|||
Data Log
|
Maximum demanded kWh and the time it happened.
|
|||
SOE
|
up to 200 pcs, record on-off status of DO/DI
|
|||
Pulse Output
|
Active optocoupler pulse output with open collector
|
|||
Multi-rate/Tariff
|
4 time zones & 12 time periods
|
Expanded Module
|
Description
|
|||
AWT100
Communication
Module
|
4G (Global general module)
|
|||
2G
|
||||
LoRaWAN (868 MHz, 923MHz)
|
||||
LoRa (460~510 MHz)
|
||||
NB-IoT
|
||||
-MK
Swtich
Module
|
12 × DI (input)
|
Dry contact input with built-in power supply
|
||
4 × DO (output)
|
Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A
|
|||
Power Supply
|
DC 12V;consumption:≤1W;RJ45 interface
|
|||
Communication
|
RJ45 interface; MODBUS-RTU (communication with main body)
|
|||
-MTC
Temperature
&
Residual Current
Measuring
Module
|
Temperature Measurement
|
-20ºC~+100ºC
|
||
Residual Current Measurement
|
10~3000 mA
|
|||
Accuracy
|
Temperature:± 2ºC; Residual Current:1% (Class 1)
|
|||
Power Supply
|
DC 12V;consumption:≤1W;RJ45 interface
|
|||
Communication
|
RJ45 interface; MODBUS-RTU (communication with main body)
|
Parameters
|
Description
|
|||
Input
|
Voltage
|
AC 3×220V/380V
|
||
Overload: 1.2 times of rated value (continuous); 2 times of rated
value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Current
|
AC 5A,100A,400A,600A;(external open-type CT)
|
|||
Overload: 1.2 times of rated value (continuous); 10 times
of rated value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Frequency
|
45~65Hz
|
|||
Measuring
Accuracy
|
Voltage&Current
|
Class 0.5
|
||
Active Power
|
Class 1
|
|||
Reactive Power
|
Class 2
|
|||
Frequency
|
0.05Hz
|
|||
2~31st harmonic
|
± 1%
|
|||
Auxiliary Power
|
AC/DC 85~265V;consumption≤10VA;
|
|||
EMC
|
Better than grade 3
|
|||
Safety
|
Withstand Voltage
|
>AC 2000V/1min
|
||
Insulation Resistance
|
>100MΩ
|
|||
Environment
|
Working Temperature
|
-20ºC~+60ºC
|
||
Storage Temperature
|
-40ºC~+70ºC
|
|||
Humidity
|
≤95% (No condensation)
|
|||
Altitude
|
≤2500m
|
Paired CT
|
Primary Current
|
Secondary Current
|
Aperture(Hole size)
|
Accuracy Class
|
AKH-0.66/K-φ10N
|
5A
|
1.25mA
|
10mm
|
Class 0.5
|
AKH-0.66/K-φ16N
|
100A
|
20mA
|
16mm
|
Class 0.5
|
AKH-0.66/K-φ24N
|
400A
|
100mA
|
24mm
|
Class 0.5
|
AKH-0.66/K-φ36N
|
600A
|
100mA
|
36mm
|
Class 0.5
|
AKH-0.66-L-45
(for residual current)
|
/
|
/
|
/
|
Class 1
|
ADW210 3-phase 4-wire Power Wiring
Note: Price below Only for Reference, Contact us for your Best Quotation !!!
Shape |
Type |
Function |
FOB Shanghai |
Remarks | |
ADW200-1 |
2S ADW200-D10 |
1S |
Measurement of all electric parameters of N(1t 2, 3, 4) channels three-phase circuit Current transformer external. 1. Three phase voltage, current, zerosequence current, frequency; 2. Three phase power, total power (active, reactive, apparent) 3. Voltage and current phase angle, voltage and current imbalance 4. Voltage, current total harmonic and 2nd-31st harmonic 5. Record of extreme values of voltage, current and power in current month and last month 6. Maximum current, power demand and real-time current, power demand 7. 200 event records, recording the action of DIDO; Support over-voltage, over-current, phase failure. DI linkage and other alarm output; 8 The rate of 4 time zones and 14 time periods can be set; 9. Four quadrant electric energy. 12-month multi rate electric energy statistics 10. 31 days four quadrant and multi rate electric energy freezing; 11. Active energy Class 1.0, and reactive electric energy Class 2.0; 12. Standard function: 2DI/2DO, RS485, 1 way active pulse output (corresponding circuit can be switched) ADW200(without buttons and display), ADW210(with buttons and LCD display), ADW220(with Lora wireless communication) |
190 |
Equipped with N(1, 2, 3, 4) groups of open type current transformers, each group with 3 current transformers D10: aperture Current specification: 5A D16: aperture Current specification: 100A |
2S |
260 |
||||
3S | 325 | ||||
4S |
390 |
||||
ADW200-2 |
2S ADW200-D16 |
1S |
200 |
||
2S |
265 |
||||
3S |
340 |
||||
4S |
415 |
||||
ADW210-1 |
2S ADW210-D10 |
1S |
205 |
||
2S |
275 |
||||
3S |
340 |
||||
4S |
405 |
||||
ADW210-2 |
2S ADW210-D16 |
1S |
215 |
Equipped with N(1,2, 3, 4) groups of open type current transformers, each group with 3 current transformers. D10 aperture cpiOmm Current specification: 5A D16: aperture 4)16mm Current specification: 100A |
|
2S |
280 |
||||
3S | 355 | ||||
4S | 430 | ||||
ADW220-1 |
2S ADW220-D10 |
1S | 235 | ||
2S | 305 | ||||
3S | 370 | ||||
4S | 435 | ||||
ADW220-2 |
ADW220-D16 |
1S |
345 |
||
2S | 310 | ||||
3S |
385 |
||||
4S |
450 |
||||
Option |
MTL |
12 external NTC temperature measurement + 4 residual current measurement |
88 |
External expansion module, connected with ADW through RJ45 interface. |
|
MK |
12DI+4DO |
80 |
Jiangsu Acrel Electrical Manufacturing Co., LTD. a production base located in Jiangyin City, Wuxi, is a pilot enterprise of Jiangsu Province, which integrates informatization and industrialization. It has a well-functioned product test center, and can carry out environmental, electromagnetic compatibility, safety and reliability tests. The production process relies on advanced information management system and strict implementation of ISO 9001 management standards, which provides guarantee for industrialization and large-scale implementation of products. The annual production capacity of meters, power sensors and energy-saving cabinets is 3.5 million units, 2 million units and 10,000 sets.
Jiangsu acrel Electric is a provider of energy data services for enterprise users to consume energy (electricity, water, gas, or other energy). In combination with the characteristics of enterprise users' energy supply and distribution system, an energy metering system is designed for each user, and a fine and reasonable energy monitoring system is set up. The construction and operation system in the energy supply, reliable reasonable use of energy and electricity safety and other aspects of the user's attention to solve pain points, visual management to help companies achieve energy use data, provide scientific data to support the introduction of the implementation of energy saving measures for enterprises in the future.