Technical parameters | Values |
Number of inputs | 8/16/32 |
Input | Active wet contact(DC12V)or passive dry contact input |
Communications | RS485 port(Modbus RTU protocol),two-core shielded line |
Bus capacity | ≤32 |
Switch incident resolution | Ability to distinguish between multiple contact successive changes:When any two contacts displacement interval is greater than 1 ms,Ability to distinguish between cells (less than 2ms) can be reflected in the SOE. |
Signalling scanning speed | All channel scanning cycle time required is 1ms |
Remote signaling debounce time | All channels use the same debounce time: 1ms (can be set) |
number of sequence of events(SOE) | 1600 Groups |