ASCB1 Smart Miniature Circuit Breaker (MCB)
Model
|
ASCB1-63
|
ASCB1LE-63
|
|
Pole
|
1P/2P/3P/4P
|
2P/4P
|
|
Grade of Shell
|
63A
|
||
Rated Voltage
|
230V(1P/2P),400V(3P/4P)
|
||
Instantaneous Unbuckle Type
|
6A,10A,16A,20A,25A,32A,40A,50A,63A
|
||
Rated Short-circuit Breaking Capacity
|
6000A
|
||
Protect
|
Over-current Protection
|
Default 100% rated current alert,
110% Rated current trip with adjustable threshold |
|
Short-circuit Protection
|
5-10 Rated current for 0.04 seconds for circuit break protection
|
||
Overload Protection
|
Default 100% rated power alert,110% Rated power trip with adjustable threshold
|
||
Over-voltage Protection
|
Default 110% rated voltage alert,120% rated voltage trip with adjustable threshold
|
||
Under-voltage Protection
|
Default 90% rated voltage alert,80% rated voltage trip with adjustable threshold
|
||
Over-temperature Protection
|
Default 80ºC alert,100ºC trip, the threshold is adjustable
|
||
Leakage Protection
|
No
|
Manual button self-inspection
|
|
Mechanical Life
|
20000 times
|
||
Electrical Life
|
6000 times
|
||
Levels of Protection
|
IP20
|
||
Connection Capacity
|
1-35mm²
|
||
Elevation Requirements
|
2000m
|
||
Ambient Temperature
|
'-10ºC~55ºC,the average temperature at 24h was no higher than 40ºC
|
||
Environmental Requirements
|
No explosion hazard, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibration
|
||
Relative Humidity
|
At + 40ºC, the relative humidity of the air is 50% and can have high relative humidity at lower temperatures
|
||
Storage Temperature
|
'-20ºC-70ºC
|
||
Class of Pollution
|
II
|
||
Installation Type
|
III
|
||
Way to Installation
|
Standard 35mm guide rail installation
|
Q: Can the circuit breaker data be collected through RS485 communication?
A: The circuit breaker has its own RS485 communication interface, and it does not need to be equipped with an ASCB1-M gateway to access the customer system, but the customer needs to provide the circuit breaker with DC12V 12A auxiliary power supply
Q: How many circuit breakers can a gateway carry?
A: 16PCS
Q: How Gateways and Circuit Breakers are Networked?
A: The gateway and the circuit breaker are connected by a 4pin cable, a set of DC12V auxiliary power supply, and a set of RS485 communication lines.
The connection between the circuit breaker and the circuit breaker is the same.
One-key addressing operation through the gateway
Q: Does the circuit breaker need to be equipped with additional accessories?
A: 1. Internally integrate various sensor modules, including: current sensor, leakage transformer, temperature sensor, etc.;
2. The circuit breaker integrates the release function, which can realize remote opening and closing operations;
3. Configure the circuit breaker network cable