Customization: | Available |
---|---|
Display: | Digital |
Installation: | Indirect Connected |
Still deciding? Get samples of US$ 103.6/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Dual Independent DC Circuits Monitoring For Twin EV Charger&Battery Voltage Input:DC 0~1000V Current Input (by Shunt): 0~75mV Current Input (by Hall Sensor): 0~5V, 0~10V, 0~20mA, 4~20mA |
|
Built-in Bipolar Power Source Range: DC -12V ~ DC +12V |
|
Optional Dual RS485 Communication 1 RS485 (standard) |
|
DO/DI Function 2 DO (2A/30V DC; 2A/250V AC) 2 DI (dry contact) |
Technical parameters |
|
Indicators |
|
Input |
Nominal value |
Voltage input range |
Current input |
DC 0-1000V See the physical wiring diagram |
Shunt:0-75mV; Hall sensor:0-20mA,4-20mA,0-5V,0-10V and so on. |
||
Overload |
1.2 times rated (continuous); 2 times rated/1 second; |
||
Power consumption |
Voltage: ≤0.2VA, current ≤0.1VA |
||
Accuracy class |
Class 1 |
||
Function |
Display |
8-bit segment LCD screen (LCD) |
|
Communication Interface |
RS485, infrared |
||
Communication protocol |
Modbus-RTU,DL/T 645-2007 |
||
Switch |
Switch output |
2 Relay outputs, 2A/30VDC or 2A/250VA |
|
Switch input |
2 dry contact inputs |
||
Pulse output |
A second pulse output, a energy pulse output |
||
See the SYS->PLUS display in the meter menu setting For example: The meter displays 100, which is 100imp/kWH |
|||
Power Supply |
Voltage range |
AC/DC 85-265V or DC24V(±10%) or DC48V(±10%) |
|
Power consumption |
≤ 3W |
||
Power frequency withstand voltage |
Power supply // Voltage input // Current input // Relay output and switch input // Communication interface / / Pulse output 3kV/1minPower supply // Relay output // Voltage input // Current input 3kV/1minPulse output // Communication interface // Switch input 2kV/1min |
||
Insulation resistance |
≥ 40M Ω |
||
Average barrier-free working hours |
≥50000h |
||
Environment |
Temperature |
Normal operating temperature: -25 °C ~ +65 °C; Limit working temperature: -40 °C ~ +70 °C; Storage temperature: -40ºC~+80ºC |
|
Humidity |
≤93%RH, no condensation, no corrosive gas |
||
Altitude |
≤2500m |
Wiring with Shunt
|
Wiring with Hall Sensor
|
Practical Application in Solar PV with Energy Storage Inverter
|
Practical Application in Solar PV with on-grid Inverter |